§ 15.100.530 — Fire-damper temperature rating

Sacramento City Code (current through Supplement No. 4, July 2026, and Ord. 2026-0022) · Sacramento City Code § 15.100.530

Corpus is an independent public-information project, not the official City of Sacramento website. Stable reference URL

15.100.530 Fire-damper temperature rating.

Selection of fire damper temperature ratings and other damper control temperature ratings shall be so that smoke removal is not impaired. A. Dampers shall have a minimum smoke rating of Class II as per the 1989 U.B.C. Standard 43-12. B. Where equipment is used for smoke removal and located in the air stream, such as air ducts, shafts, or plenum ceiling areas, the devices used shall have a temperature rating equal to, or greater than, the maximum working temperature that could be encountered under removal conditions. These devices shall include, but not be limited to, motorized dampers, air-volume controls, pneumatic piping and wiring. (Prior code §§ 9.28.1252, 15.13.1306)