§ 15.100.730 — Seismic consideration
Sacramento City Code (current through Supplement No. 4, July 2026, and Ord. 2026-0022) · Sacramento City Code § 15.100.730
Corpus is an independent public-information project, not the official City of Sacramento website. Stable reference URL
15.100.730 Seismic consideration.
The anchorage of all equipment required by this section shall be designed in accordance with Section 2312 of the Uniform Building Code, for a lateral force based on a Cp value of 0.75, unless data substantiating a lesser value is furnished. Verification of such conformance shall be substantiated by a licensed structural engineer for the following equipment: A. Elevator drive and suspension systems; B. Standby and emergency power including lighting facilities; C. Fire pumps, automatic fire extinguishing system, including piping and other fire protection equipment; D. Air-handling equipment regulated by this title; E. Fire alarm equipment; F. Helistops. (Prior code §§ 9.28.1272, 15.16.1601)
