§ 15.100.750 — Location

Sacramento City Code (current through Supplement No. 4, July 2026, and Ord. 2026-0022) · Sacramento City Code § 15.100.750

Corpus is an independent public-information project, not the official City of Sacramento website. Stable reference URL

15.100.750 Location.

Fire pumps and associated equipment shall be located in a separate two-hour fire resistive room. There shall be no other equipment in the room. A. Location of the fire pumps, diesel fuel tanks, and controls shall be approved by the authority having jurisdiction prior to installation. B. When a fire pump is located in a basement or other areas subjected to flooding, sump pump(s) shall be installed. Sump pumps shall be connected to the standby power system. The sump water level shall be monitored in the fire control room. A "trouble" signal shall be transmitted when water level rises above normal. (Prior code §§ 9.28.1274, 15.17.1702)

§ 15.100.750 — Location | Sacramento, CA City Code (current through Supplement No. 4, July 2026, and Ord. 2026-0022) | Corpus