§ 27-423 Exit requirements.
In every room containing a boiler, furnace, or incinerator, the maximum travel distance from any point within the room to an exit shall not exceed fifty feet. When two or more exits are so required, only the main exit shall comply with the size and construction requirements of subchapter six of this chapter. The other exit or exits may be noncombustible ladders or stairs leading to exit openings not less than thirty-two inches by forty-eight inches.