Section 362.10
Section 362.10(2) – Revise the opening paragraph of Item (2) in the list of items in Section 362.10 to read as follows: (2) In any building exceeding 3 floors above grade, ENT shall be concealed within walls, floors, and ceilings where the walls, floors, and ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies. The 1-hour-finish-rated thermal barrier shall be permitted to be used for combustible or noncombustible walls, floors, and ceilings. Section 362.10(2) – Revise the Exception in Section 362.10(2) to read as follows: Exception to (2): DELETED. Section 362.10(5) – Revise Item (5) in the list of items in Section 362.10 to read as follows: (5) Above suspended ceilings where the suspended ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies, except as permitted in 362.10(1)(a). Section 362.10(5) – Revise the Exception at the end of Section 362.10(5) to read as follows: Exception to (5): DELETED.