14A-8-803.1 Mercantile, industrial, and storage uses.
Where a story, room, or space is used or intended to be used for mercantile, industrial, or storage purposes and has a floor designed for live loads exceeding 100 psf (4.80 kN/m2), the design live load must be conspicuously posted at or near the primary entrance to each story, room, or space, using durable signs supplied by the owner with characters not less than 2 inches (51 mm) in height. Where more than half but less than all of a story, room, or space is designed for live loads exceeding 100 psf (4.80 kN/m2), a durable floor plan indicating areas that are designed for lesser live loads must be posted in a conspicuous place at each exit from the story, room, or space. It is unlawful to remove or deface such signs.
Exceptions:
1. Posting of floor loads is not required in buildings or portions thereof used exclusively for the production and distribution of electricity, gas, or steam.
2. Where floor loads are posted in accordance with requirements in effect at the time of construction or alteration.