NYC Electrical Code § 701.11
NYC Electrical Code § 701.11
in effectSection 701.11
Section 701.11 – Add a new Section 701.11 to read as follows:
701.11 Generator Supply Conductors without Overcurrent Protection.
(A) Conductors Ampacity. See 445.13 of this code.
(B) Installation of Generator Conductors. Conductors from the generator output terminal to the first overcurrent device shall be installed in accordance with 230.6.
(C) Overcurrent Devices. The number of overcurrent devices supplied by the generator shall not be limited.