Vent for future fixtures.
Municipal Code of Chicago § 18-29-905.7
in effect18-29-905.7 Vent for future fixtures.
Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed a minimum of one-half the diameter of the drain, but not less than the minimum size indicated in Table 18-29-916.1. The vent rough-in shall connect to the vent system. The connection shall be identified to indicate that the connection is a vent.