NYC Electrical Code § 695.14
NYC Electrical Code § 695.14
in effectSection 695.14
Section 695.14(E)– Revise Section 695.14(E) to read as follows:
(E) Electric Fire Pump Control Wiring Methods. All electric motor-driven fire pump control wiring shall be in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing with watertight fittings.
Section 695.14(F) – Add exception at the end of Section 695.14(F) to read as follows:
Exception to 695.14(F)(1) and (F)(2): The control conductors located in the electrical equipment room where they originate and in the fire pump room shall not be required to have the minimum 2-hour fire separation or fire resistance rating.