SEPARATION FROM COMBUSTIBLE MATERIAL.
Los Angeles Municipal Code § 57.2404.7.9.4
in effectSEC. 57.2404.7.9.4. SEPARATION FROM COMBUSTIBLE MATERIAL.
Ducts or pipes may be separated from combustible material by a ventilated collar which provides a clear air space equal to one-half the diameter of the duct, but in no event shall such collar provide less than 3-inch air space, and such collar shall extend not less than 12 inches above and below such combustible material.
Source: City of Los Angeles, Charter and Codes (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/los_angeles/latest/lamc/0-0-0-348568Fetched: 10/24/2026