Clearances.
Municipal Code of Chicago § 18-28-506.3.7
in effect18-28-506.3.7 Clearances.
Grease duct systems serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm).
Exception: Listed and labeled factory-built commercial kitchen grease ducts installed in accordance with the Chicago Fire Prevention Code.
(Amend Coun. J. 9-14-21, p. 35949, Art. V, § 13)