BASIC PROVISIONS.
Los Angeles Municipal Code § 91.2700
in effectSEC. 91.2700. BASIC PROVISIONS.
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Chapter 27 of the CBC is hereby adopted by reference, except that Los Angeles Municipal Code Subsections 91.2702.2.11.1, 91.2702.2.16.1, and 91.2702.2.19.1 are added.
91.2702.2.11.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)
91.2702.2.16.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)
91.2702.2.19.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)
Source: City of Los Angeles, Charter and Codes (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/los_angeles/latest/lamc/0-0-0-176061Fetched: 10/24/2026