NYC Electrical Code § 805.133
NYC Electrical Code § 805.133
in effectSection 805.133
Section 805.133 – Revise the opening paragraph in Section 805.133 to read as follows:
805.133 Installation of Communications Wires, Cables, and Equipment. Communications wires and cables from the protector to the equipment or, where no protector is required, communications wires and cables attached to the outside or inside of the building shall comply with 805.133(A) through 805.133(C).
Section 805.133(C) – Add a new Section 805.133(C) to read as follows:
(C) Electrical Equipment Rooms. Communications equipment and cabling shall not be installed in Electrical Equipment Rooms.
Exception No. 1: Communications equipment and cabling for control and monitoring of electrical equipment or associated components, or both, shall be permitted.
Exception No. 2: Antenna and associated cabling intended for emergency life-safety use shall be permitted.
Source: City of New York, Charter, Administrative Code and Rules (American Legal Publishing XML export, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/newyorkcity/latest/NYCadmin/0-0-0-233134Fetched: 10/24/2026