Quantity - Emergency conditions.
Municipal Code of Chicago § 18-28-1105.8.4
in effect18-28-1105.8.4 Quantity - Emergency conditions.
Upon actuation of the refrigerant detector required in Section 18-28-1105.5, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity:
[image omitted; see the official code]
where:
Q = The airflow in cubic feet per minute (m3/s).
G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room.