HAZARDOUS MATERIALS STORAGE TANKS INSIDE BUILDINGS.
Los Angeles Municipal Code § 57.5003.2.2.3
in effectSEC. 57.5003.2.2.3. HAZARDOUS MATERIALS STORAGE TANKS INSIDE BUILDINGS.
Tanks for the storage of hazardous materials in liquid form inside buildings shall be provided with any of the following:
1. A normally closed remotely-activated valve.
2. An automatic-closing heat-activated valve.
3. An approved device on each liquid transfer connection below the liquid level that shall provide a quick cut-off of flow in the event of fire.