Section BC 506: Building Area Modifications
506.1 General.
The floor area of a building shall be determined based on the type of construction, occupancy classification, whether there is an automatic sprinkler system installed throughout the building and the amount of building frontage on public way or open space.
506.1.1 Unlimited area buildings.
Unlimited area buildings shall be designed in accordance with Section 507.
506.1.2 Special provisions.
The special provisions of Section 510 permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable areas of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in Section 510.
506.1.3 Basement and cellar.
A single basement or cellar need not be included in the total allowable building area, provided such basement or cellar does not exceed the area permitted for a building with no more than one story above grade plane.
506.2 Allowable area determination.
The allowable area of a building shall be determined in accordance with the applicable provisions of Sections 506.2.1 through 506.2.4, and Section 506.3.
Table 506.2 a
Allowable Area Factor (At = NS, S1, S13D, S13R, or SM, as applicable) in Square Feet
Occupancy Classification See Footnotes Type of Construction
Type I Type II Type III Type IV i Type V
A B A B A B HT A B
A-1 NS b, c UL UL 17,500 10,500 14,700 5,600 15,000 8,400 5,500
S1 UL UL 52,500 31,500 44,100 16,800 45,000 25,200 16,500
SM UL UL 35,000 21,000 29,400 11,200 30,000 16,800 11,000
A-2 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500
S1 UL UL 52,500 28,500 42,000 16,800 45,000 25,200 16,500
SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000
A-3 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500
S1 UL UL 52,500 28,500 42,000 16,800 45,000 25,200 16,500
SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000
A-4 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500
S1 UL UL 52,500 28,500 42,000 16,800 45000 25,200 16,500
SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000
A-5 NS b, c UL UL UL UL UL UL UL UL UL
S1
SM
B NS b, c UL UL 37,500 10,500 28,500 5,600 36,000 8,400 5,500
S1 UL UL 112,500 31,500 85,500 16,800 108,000 25,200 16,500
SM UL UL 75,000 21,000 57,000 11,200 72,000 16,800 11,000
E NS b, c UL UL 26,000 10,500 23,500 5,600 25,500 8,400 5,500
S1 UL UL 78,000 31,500 70,500 16,800 76,500 25,200 16,500
SM UL UL 52,000 21,000 47,000 11,200 51,000 16,800 11,000
F-1 NS b, c UL UL 12,500 7,500 7,500 3,000 10,000 3,000 1,000
S1 UL UL 37,500 22,500 22,500 9,000 30,000 9,000 3,000
SM UL UL 25,000 15,000 15,000 6,000 20,000 6,000 2,000
F-2 NS b, c UL UL 37,500 10,500 28,500 5,600 30,000 8,400 5,500
S1 UL UL 112,500 31,500 85,500 16,800 90,000 25,200 16,500
SM UL UL 75,000 21,000 57,000 11,200 60,000 16,800 11,000
H-1 NS b, c 21,000 16,500 11,000 7,500 9,500 7,000 10,500 7,500 NP
S1
H-2 f NS b, c 21,000 16,500 11,000 7,500 9,500 7,000 10,500 7,500 3,000
S1
SM
H-3 f NS b, c UL 60,000 26,500 14,000 17,500 13,000 25,000 10,000 5,000
S1
SM
H-4 NS b, c UL UL 37,500 17,500 28,500 17,500 36,000 18,000 6,500
S1 UL UL 112,500 52,500 85,500 52,500 108,000 54,000 19,500
SM UL UL 75,000 35,000 57,000 35,000 72,000 36,000 13,000
H-5 NS b, c UL UL 37,500 23,000 28,500 19,000 36,000 18,000 9,000
S1 UL UL 112,500 69,000 85,500 57,000 108,000 54,000 27,000
SM UL UL 75,000 46,000 57,000 38,000 72,000 36,000 18,000
I-1 NS b, c UL UL 19,000 NP 16,500 5,600 18,000 NP NP
S13D UL UL 19,000 NP 16,500 5,600 18,000 NP NP
S1 UL UL 57,000 49,500 16,800 54,000 NP NP
SM UL UL 38,000 NP 33,000 11,200 36,000 NP NP
I-2 NS b, c UL UL 7,000 3,500 5,000 1,200 6,500 2,000 NP
S1 UL UL 21,000 10,500 15,000 3,600 19,500 6,000 NP
SM UL UL 14,000 7,000 10,000 2,400 13,000 4,000 NP
I-3 NS b, c UL UL 7,000 3,500 5,000 1,200 6,500 2,000 NP
S1 UL UL 21,000 10,500 15,000 3,600 19,500 6,000 NP
SM UL UL 14,000 7,000 10,000 2,400 13,000 4,000 NP
I-4 NS b, c UL UL 26,500 9,500 23,500 5,600 25,500 8,400 5,500
S1 UL UL 79,500 28,500 70,500 16,800 76,500 25,200 16,500
SM UL UL 53,000 19,000 47,000 11,200 51,000 16,800 11,000
M NS b, c UL UL 21,500 7,500 18,500 5,600 14,000 8,400 5,500
S1 UL UL 64,500 22,500 55,500 16,800 42,000 25,200 16,500
SM UL UL 43,000 15,000 37,000 11,200 28,000 16,800 11,000
R-1 NS b, c UL UL UL NP 24,000 NP 20,500 NP NP
S13R
S1 UL UL UL NP 72,000 NP 61,500 NP NP
SM UL UL UL NP 48,000 NP 41,000 NP NP
R-2 NS b, c UL UL UL NP 24,000 5,600 20,500 NP NP
S13R
S1 UL UL UL NP 72,000 16,800 61,500 NP NP
SM UL UL UL NP 48,000 11,200 41,000 NP NP
R-3 NS b, c UL UL 17,500 10,500 14,700 5,600 30,000 8,400 g, h 5,500 g
S13D 5,600
S13R
S1 UL UL 52,500 31,500 44,100 16,800 90,000 8,400 g, h 5,500 g
SM UL UL 35,000 21,000 29,400 11,200 60,000
S-1 NS b, c UL 48,000 12,000 7,500 7,500 7,500 7,500 5,000 1,000
S1 UL 144,000 36,000 22,500 22,500 22,500 22,500 15,000 3,000
SM UL 96,000 24,000 15,000 15,000 15,000 15,000 10,000 2,000
S-2 d, e NS b, c UL UL 15,000 10,000 10,000 8,500 10,000 8,400 5,500
S1 UL UL 45,000 30,000 30,000 25,500 30,000 25,200 16,500
SM UL UL 30,000 20,000 20,000 17,000 20,000 16,800 11,000
U e NS b, c UL 35,000 19,000 8,500 14,000 8,500 18,000 9,000 5,500
S1 UL 105,000 57,000 25,500 42,000 25,500 54,000 27,000 16,500
SM UL 70,000 38,000 17,000 28,000 17,000 36,000 18,000 11,000
= Not permitted in Fire District = Not permitted in Fire District without sprinklers
Note: UL = Unlimited; NP = Not permitted.
For SI: 1 square foot = 0.0929 m2.
NS = Buildings not equipped throughout with an automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
a. See the following sections for general exceptions to Table 506.2.
1. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
2. Section 506.3, Allowable area increase due to frontage.
3. Section 507, Unlimited area building.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. The NS value is only for use in buildings not required by this code to be equipped throughout with an automatic sprinkler system.
d. For open parking structures, see Section 406.5.
e. For private garages, see Section 406.3.
f. See Section 415.8 for limitations.
g. See Exception 9 of Section D105.1 for allowances of Type VA and VB construction for R-3 occupancies.
h. See Exception 12 of Section D105.1 for allowances of Type VA construction for R-3 occupancies in Lower Density Growth Management Areas.
i. Type IV construction utilizing cross-laminated timber or structural composite lumber shall be sprinklered where required by Section 903.2.13.
506.2.1 Single-occupancy, one-story buildings.
The allowable area of a single-occupancy building with no more than one story above grade plane shall be determined in accordance with Equation 5-1:
Aa = At + (NS × If ) (Equation 5-1)
where:
Aa = Allowable area (square feet).
At = Tabular allowable area factor (NS, S1, S13D or S13R value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for nonsprinklered building (regardless of whether the building is sprinklered).
If = Area increase factor due to frontage (percent) as calculated in accordance with Section 506.3.
506.2.2 Mixed-occupancy, one-story buildings.
The allowable area of a mixed-occupancy building with no more than one story above grade plane shall be determined in accordance with the applicable provisions of Section 508.1 based on Equation 5-1 for each applicable occupancy.
506.2.2.1 Group H-2 or H-3 mixed occupancies.
For a building containing Group H-2 or H-3 occupancies, the allowable area shall be determined in accordance with Section 508.4.2, with the sprinkler system increase applicable only to the portions of the building not classified as Group H-2 or H-3.
506.2.3 Single-occupancy, multistory buildings.
The allowable area of a single-occupancy building with more than one story above grade plane shall be determined in accordance with Equation 5-2:
Aa = [At + (NS × If )] × Sa (Equation 5-2)
where:
Aa = Allowable area (square feet).
At = Tabular allowable area factor (NS, S13D, S13R or SM value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for a nonsprinklered building (regardless of whether the building is sprinklered).
If Area factor increase due to frontage (percent) as calculated in accordance with Section 506.3.
Sa Actual number of building stories above grade plane, not to exceed three. For buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2, use the actual number of building stories above grade plane, not to exceed four.
No individual story shall exceed the allowable area (Aa) as determined by Equation 5-2 using the value of Sa = 1.
506.2.4 Mixed-occupancy, multistory buildings.
Each story of a mixed-occupancy building with more than one story above grade plane shall individually comply with the applicable requirements of Section 508.1. For buildings with more than three stories above grade plane, the total building area shall be such that the aggregate sum of the ratios of the actual area of each story divided by the allowable area of such stories, determined in accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall not exceed three.
Aa = [At + (NS × If )] (Equation 5-3)
where:
Aa = Allowable area (square feet).
At = Tabular allowable area factor (NS, S13D, S13R or SM value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for a nonsprinklered building (regardless of whether the building is sprinklered).
If = Area factor increase due to frontage (percent) as calculated in accordance with Section 506.3.
Exception: For buildings designed as separated occupancies under Section 508.4 and equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2, the total building area shall be such that the aggregate sum of the ratios of the actual area of each story divided by the allowable area of such stories determined in accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall not exceed four.
506.2.4.1 Group H-2 or H-3 mixed occupancies.
For a building containing Group H-2 or H-3 occupancies, the allowable area shall be determined in accordance with Section 508.4.2, with the sprinkler system increase applicable only to the portions of the building not classified as Group H-2 or H-3.
506.3 Frontage increase.
Area factor increase shall be determined in accordance with Sections 506.3.1 through 506.3.3.
506.3.1 Minimum percentage of perimeter.
To qualify for an area factor increase based on frontage, a building shall have not less than 25 percent of its perimeter on a public way or open space. Such open space shall be either on the same zoning lot or dedicated for public use and shall be accessed from a street or approved fire lane.
506.3.2 Minimum frontage distance.
To qualify for an area factor increase based on frontage, the public way or open space adjacent to the building perimeter shall have a minimum distance (W) of 20 feet (6096 mm) measured at right angles from the building face to any of the following:
1. The closest interior tax lot line.
2. The entire width of a street, alley or public way.
3. The exterior face of an adjacent building on the same tax lot.
Where the value of W is greater than 30 feet (9144 mm), a value of 30 feet (9144 mm) shall be used in calculating the building area increase based on frontage, regardless of the actual width of the public way or open space. Where the value of W varies along the perimeter of the building, the calculation performed in accordance with Equation 5-5 shall be based on the weighted average calculated in accordance with Equation 5-4.
W = (L1 × w1 + L2 × w2 + L3 × w3…)/F (Equation 5-4)
where:
W = (Width: weighted average) = Calculated width of public way or open space (feet).
Ln = Length of a portion of the exterior perimeter wall.
wn = Width (≥ 20 feet) of a public way or open space associated with that portion of the exterior perimeter wall.
F = Building perimeter that fronts on a public way or open space having a width of 20 feet (6096 mm) or more.
Exception: Where a building meets the requirements of Section 507, as applicable, except for compliance with the minimum 60-foot (18 288 mm) public way or yard requirement, and the value of W is greater than 30 feet (9144 mm), the value of W shall not exceed 60 feet (18 288 mm).
506.3.3 Amount of increase.
The area factor increase based on frontage shall be determined in accordance with Equation 5-5:
If = (F/P - 0.25) W/30 (Equation 5-5)
where:
If = Area increase factor due to frontage.
F = Building perimeter that fronts on a public way or open space having minimum distance of 20 feet (6096 mm).
P = Perimeter of entire building (feet).
W = Width of public way or open space (feet) in accordance with Section 506.3.2.