Auxiliary supervised annunciation.
Sacramento City Code § 15.100.280
in effect15.100.280 Auxiliary supervised annunciation.
An auxiliary supervised annunciation system shall be installed in the fire control room. A "trouble condition" in these systems shall be indicated by an audible signal and a visual display that clearly indicates the following:
A. Low fuel status (when fuel level falls below minimum required amount) for:
1. Standby and emergency generator(s), and
2. Fire pump(s);
B. Low water status of the auxiliary water supply (below minimum required amount);
C. Fire pump(s) running;
D. Generator(s) running;
E. Fire department breathing air system.
(Note: Where a trouble condition exists on any of the above items a system trouble shall be transmitted.)
This may be integrated within the main fire alarm annunciator panel. (Prior code §§ 9.28.1227, 15.11.1108)