NYC Electrical Code § 725.144
NYC Electrical Code § 725.144
in effectSection 725.144
Section 725.144 – Revise the first sentence in Section 725.144 to read as follows:
725.144 Transmission of Power and Data. Sections 725.144(A), (B), and (C) shall apply to Class 2 and Class 3 circuits that transmit power and data to a powered device.
Section 725.144(C) – Add a new Section 725.144(C) to read as follows:
(C) Use of Class 2-LP or Class 3-LP Cables to Transmit Power and Data for Emergency and Egress Lighting Systems.
(1) System design shall be permitted by qualified persons under engineering supervision.
(2) System Design shall be in accordance with requirements as listed In Article 700 Emergency Systems.