§ 15-26-820 — Bulk oxygen storage systems

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 15-26-820

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

15-26-820 Bulk oxygen storage systems.

Bulk oxygen storage systems shall be located aboveground out of doors or shall be installed in a building of Type I or II construction, adequately vented, and used for that purpose only. The minimum clearances to buildings shall be 50 feet, and ten feet to streets or sidewalks. Where stored as a liquid, asphaltic or bituminous paving shall not be used within ten feet. (Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 63)