§ 18-28-1101.14 — Safety equipment
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1101.14
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL
18-28-1101.14 Safety equipment.
Two self-contained breathing air apparatuses (SCBA), minimum 30 minutes rated, approved by the Bureau of Mines of the United States Department of the Interior, shall be kept outside the entrance to the Machinery Room. If a Group 3 Refrigerant is used, two suits of full protective clothing that meet the Occupational Safety and Health Administration (OSHA.) Fire Brigade Standard (29 C.F.R. 1910.156) must be provided and kept in the same cabinet.