18-28-1105.7 Fuel-burning appliance.

Open flames that use combustion air from the machinery room shall not be installed in a machinery room, when said machinery room is required by Section 18-28-1104.2. Exceptions: 1. Matches, lighters, halide leak detectors and similar devices. 2. Where the refrigerant is carbon dioxide or water. 3. Fuel-burning appliances shall not be prohibited in the same machinery room with refrigerant- containing equipment or appliances where combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leakage from entering the combustion chamber.