§ 18-28-1105.9 — Termination of relief devices

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1105.9

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

18-28-1105.9 Termination of relief devices.

Pressure-relief devices, and purge systems located within the machinery room shall terminate outside of the structure at a location not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit.