§ 18-28-504.4.1 — Termination location

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-504.4.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

18-28-504.4.1 Termination location.

Exhaust duct terminations shall be installed in accordance with the dryer manufacturer's instructions. Where the manufacturer's instructions do not specify a termination location, the exhaust duct shall terminate not less than 3 feet (914 mm) in any direction from openings into buildings, including openings in ventilated soffits. Exhaust duct terminations shall not be located in exterior walls which are not permitted to have unprotected openings in accordance with the Chicago Building Code. (Amend Coun. J. 9-14-21, p. 35949, Art. V, § 11)