§ 18-28-506.3.2 — Grease duct materials

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-506.3.2

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

18-28-506.3.2 Grease duct materials.

Grease ducts serving a Type I hood shall be constructed of steel not less than 0.055 inch (1.4 mm) (No. 16 Gauge) in thickness or stainless steel not less than 0.044 inch (1.1 mm) (No. 18 Gauge) in thickness.