For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-604.8 — Lining installation

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-604.8

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

18-28-604.8 Lining installation.

Linings shall be interrupted at the area of operation of a fire damper and at a minimum of 6 inches (152 mm) upstream of and 6 inches (152 mm) downstream of electric-resistance and fuel-burning heaters in a duct system. Metal nosings or sleeves shall be installed over exposed duct liner edges that face opposite the direction of air flow.

§ 18-28-604.8 — Lining installation | Chicago, IL — Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) | Corpus