§ 18-29-904.5 — Location of vent terminal
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-904.5
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL
18-29-904.5 Location of vent terminal.
An open vent terminal from a drainage system shall not be located directly beneath a door, openable window, overhead or other ventilating intake opening of the building or of an adjacent building, nor shall any such vent terminals be within 10 feet (3.05 m) horizontally of such an opening unless the vent terminal is at least 3 feet (914 mm) above the top of such opening. (Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 3)