14B-26-2606 Light-transmitting plastics.
The provisions of Section 2606 of IBC are adopted by reference with the following modifications: 1. In provisions adopted by reference, reset the following terms in italic type: "approved"; "greenhouse" and "light- diffusing system." 2. Revise items 1 and 2 of Section 2606.7 to read: "1. Group A with an occupant load of 300 or more. 2. Group E." 3. Revise item 5 of Section 2606.7 to read: "5. Interior exit stairways, interior exit ramps and exit passageways. 4. Revise Section 2606.7.4 to read: "2606.7.4 Fire suppression system. In buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, light-diffusing systems shall be protected both above and below unless the automatic sprinkler system has been approved for installation only above the light-diffusing system. Areas of light-diffusing systems that are protected in accordance with this section shall not be limited." 5. Revise Section 2606.7.5 by deleting "approved." (Amend Coun. J. 2-19-20, p. 14473, Art. II, § 90)