For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 27-883 — Gas equipment connected to chimneys

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Admin. Code § 27-883

Corpus is an independent public-information project, not the official City of New York website. Stable reference URL

§ 27-883 Gas equipment connected to chimneys.

Automatically controlled gas-fired equipment connected to a chimney that also serves equipment for the combustion of solid or liquid fuel shall be equipped with an automatic pilot. A gas-fired equipment vent connector and a chimney connector from equipment burning another fuel, located on the same floor, may be connected into the same chimney through separate openings, or may be connected through a single opening if joined by a suitable fitting located as close as practicable to the chimney. If two or more openings are provided into one chimney, they shall be at different levels.