FC 704 — Floor Openings and Shafts
New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Fire Code § FC 704
Corpus is an independent public-information project, not the official City of New York website. Stable reference URL
Section FC 704: Floor Openings and Shafts
704.1 Enclosures. Interior vertical shafts, including stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected as specified in the construction codes, including the Building Code. When openings are required to be protected by the construction codes, including the Building Code, openings into such shafts shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are allowed if the fusible link rating does not exceed 135°F (57°C).