§ 705.30

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 705.30

Corpus is an independent public-information project, not the official City of New York website. Stable reference URL

Section 705.30

Section 705.30 – Revise Section 705.30(C) to read as follow: (C) Transformers. The following apply to the installation of transformers: (1) For the purpose of overcurrent protection, the primary side of transformers with sources on each side shall be the side connected to the largest source of available fault current. (2) Transformer secondary conductors shall be protected in accordance with 240.21(C).