For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 760.48

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 760.48

Corpus is an independent public-information project, not the official City of New York website. Stable reference URL

Section 760.48

Section 760.48 – Revise Section 760.48(A) to read as follows: 760.48 Conductors of Different Circuits in Same Cable, Enclosure, or Raceway. (A) NPLFA Circuits. Non-power limited fire alarm circuit conductors shall not be permitted to occupy the same cable, enclosure, or raceway with circuit conductors of other systems. Section 760.48 – Revise Section 760.48(B) to read as follows: (B) Fire Alarm with Power-Supply Circuits. Power supply and fire alarm circuit conductors shall be permitted in the same enclosure only where connected to the same equipment.