NYC Electrical Code § 760.46
NYC Electrical Code § 760.46
in effectSection 760.46
Section 760.46 – Revise Section 760.46 to read as follows:
760.46 NPLFA Circuit Wiring. Installation of non-power limited fire alarm feeders and branch circuits shall be in accordance with applicable portions of 110.3(B), 300.7, 300.11, 300.15, 300.17, 300.19(B) and other appropriate articles of Chapter 3 using raceway methods described in Articles 342, 344, and 358, or use Type MI Cable in accordance with Article 332. For the last 3 ft (914 mm) of NPLFA branch circuit, a Flexible Metallic Conduit (FMC) or Liquidtight Flexible Metallic Conduit (LFMC) shall be permitted.
Exception No. 1: As provided in 760.48 through 760.52.
Exception No. 2: This section does not apply where other articles of this Code require other methods.
Exception No. 3: Where other articles of this code require other wiring to be used, a listed electrical protective system with minimum 2-hour fire rating shall be permitted.