Section 760.43 – Revise Section 760.43 to read as follows:
760.43 NPLFA Circuit Overcurrent Protection. Overcurrent protection for conductors 14 AWG and larger shall be provided in accordance with the conductor ampacity without applying the ampacity adjustment and correction factors of 310.15 to the ampacity calculation.
Exception: This section does not apply to other articles of this Code that permit or require other overcurrent protection.