18.16.060 - Section 210.71 Additional Outlets, added.
NFPA 70 National Electrical Code, 2020 Edition, Section 210.70C Additional Outlets, is hereby added to read as follows:
210.70C Additional Outlets. The following receptacle outlets shall be installed, in addition to those required by National Electrical Code, 2020 Edition, Sections 210-50 through 210-70:
(1) On wall areas over work benches, behind bars, serving counters, or other wall spaces where electrical signs or appliances may be used or installed, not less than one (1) receptacle outlet shall be installed for every six (6) feet or major fraction thereof (i.e., the second receptacle outlet shall be located a maximum of (nine) 9 feet from the beginning of the work bench, serving counter or wall space) from the edge measured horizontally along such wall parallel to the floor or ceiling.
(2) In lounges, taverns, bars or other establishments where electrical signs, appliances or similar devices may be placed on or attached to the ceiling, sufficient receptacle outlets shall be installed on the ceilings so that no point on such ceiling is more than twelve (12) feet from a receptacle outlet.
(3) In "mini-warehouse" units or similar storage occupancies designed to be leased or rented individually the following minimum requirements for lights and receptacles shall be provided:
Exterior lighting providing a minimum 2.0 foot-candle illumination at the ground level at the center of the entry door of each unit.
(Ord. No. 019528, § 1, 8-1-2023)