Fire protection.
Municipal Code of Chicago § 15-28-1190
in effect15-28-1190 Fire protection.
Every conveyor and spout between a grain bleacher and any other building shall be provided with a damper at each end. Such dampers shall be of construction having a 60-minute fire-resistive value, and shall be so arranged and equipped as to close automatically in case of fire by the release of a fusible link or by the actuation of a standard thermostatic releasing device.
(Prior code § 92-108)