NYC Electrical Code § 760.3
NYC Electrical Code § 760.3
in effectSection 760.3
Section 760.3 – Revise Section 760.3(F) to read as follows:
(F) Optical Fiber Cables. Where optical fiber cables are utilized for fire alarm circuits, the cables shall be supervised and installed in EMT, IMC or RMC and terminated in equipment listed for fire alarm use. Where installed underground between buildings, optical fiber cables shall be permitted to be installed in non-metallic conduit buried or concrete encased.
Section 760.3 – Revise Section 760.3(L) to read as follows:
(L) DELETED.
Section 760.3 – Revise Section 760.3(M) to read as follows:
(M) DELETED.
Section 760.3 – Revise the Exception to Section 760.3(O) to read as follows:
Exception: DELETED.
Source: City of New York, Charter, Administrative Code and Rules (American Legal Publishing XML export, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/newyorkcity/latest/NYCadmin/0-0-0-232885Fetched: 10/24/2026