San Diego Municipal Code § 512.0504 Ignition-Resistant Construction
§512.0504 Ignition-Resistant Construction
(a) Local Addition. Section 504.2.3, Drip Edge Flashing, is added as follows:
When drip edge flashing is used at the free edges of roofing materials, it must be non-combustible.
(b) Local Addition. Section 504.8.3, Vinyl Window Reinforcing, is added as follows:
Glazing frames made of vinyl materials shall have welded corners, metal reinforcement in the interlock area, and be certified to the most current edition of American Architectural Manufacture’s Association (AAMA)/Window and Door Manufacture’s Association (WDMA)/Canadian Standards Association
(CSA) 101/I.S.2/A440-22 structural requirements.
(“Ignition-Resistant Construction” added 1-29-2026 by O-22042 N.S.; effective 2-28-2026.)