Section 905.2 Installation Standard for Standpipe Systems, Amended.
El Paso City Code § 9.52.080.25
in effect9.52.080.25 - Section 905.2 Installation Standard for Standpipe Systems, Amended.
905.2.1 Installation Standard for Automatic Standpipe Systems, Added.
NFPA 14 11.5.1 Automatic Standpipe Flow Test/Hydraulic Verification Methods shall be field performed to confirm hydraulic design by way of methods outlined in 7.10.1 Class I and Class III Systems.
905.2.2 Installation Standard for Manual Standpipe Systems, Added.
NFPA 14 11.5.2 Manual Standpipe Flow Test/Hydraulic Verification Methods as depicted in Figure A.11.5.2(a) or Figure A.11.5.2(b) shall be done prior to system final. Contractor under FSYS permit shall be responsible for obtaining their own pump capable of flowing the required gpm and at the required pressure for the system.
Figure A.11.5.2(a) and Figure A.11.5.2(b)
[image omitted; see the official code]
(Ord. No. 019521, § 1, 7-5-2023)
Source: City of El Paso, City Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/tx/el_paso/codes/code_of_ordinances?nodeId=TIT9HESA_CH9.52FIPRCO_9.52.080.25SE905.2INSTSTSYAMFetched: 10/28/2026