Pipe Insulation
NYC Mechanical Code § MC 1204
in effectSection MC 1204: Pipe Insulation
1204.1 Insulation characteristics.
Pipe insulation installed in buildings shall conform to the requirements of the New York City Energy Conservation Code, shall be tested in accordance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231; and shall have a maximum flame spread index of 25 and a smoke-developed index not exceeding 450. Insulation installed in an air plenum shall comply with Section 602.2.1.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
1204.2 Required thickness.
Hydronic piping shall be insulated to the thickness required by the New York City Energy Conservation Code.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
Source: City of New York, Charter, Administrative Code and Rules (American Legal Publishing XML export, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/newyorkcity/latest/NYCadmin/0-0-0-196037Fetched: 10/24/2026