Electrical Work Review.
1 RCNY § 4000-01
in effect§ 4000-01 Electrical Work Review.
(a) Electrical work review. Electrical work review is required in the following circumstances:
(1) Electrical installations. Electrical Plan review (EPR) is required in accordance with Section 110.2(B) of the New York city electrical code (“Electrical Code”).
(i) A new installation of equipment totaling 1000 KVA or higher;
(ii) Any change in an installation with a rating of 1000 KVA or higher, up to and including the second level overcurrent protection, unless it was fully described and approved as “future” on the original approved plan.
(iii) Any addition to an existing installation which would bring the total to 1000 KVA or higher.
(iv) A new installation or revised installation above 600 volts, irrespective of KVA rating.
(v) The addition of any equipment in a room, which would affect clearances around the equipment of a 1000 KVA installation.
(2) Electrical equipment. Electrical equipment review is required for electrical equipment not specifically addressed in the Electrical Code Technical Standards and any other electrical equipment not bearing the label of approval of an electrical testing laboratory acceptable to the Commissioner.
(b) Filing requirements.
(1) EPR. Filings for installations referenced in paragraph (1) of subdivision (a) of this rule must comply with the following:
(i) Submission of all required documents, including all drawings, must be made in a manner prescribed by the Department, including electronically, by a New York State Licensed and Registered Professional Engineer or a New York State Licensed and Registered Architect.
(ii) A filing fee of $650.00 must be paid for each submission.
(iii) All submissions must include a one-line diagram, a plan view, and, if required, an equipment room layout and be in accordance with the following requirements:
- One line diagram
- Plan view / service equipment room layout
- Submissions must be in accordance with, and include, the following requirements:
(A) All drawings must be clear, legible, and use standard notations.
(B) Installations that are not all new must clearly mark what is new and what is existing. In addition, all new work must be encircled by a ‘bubble' or ‘cloud' on the drawings.
(C) For residential installations, the calculations justifying a de-rating of the neutral must be submitted.
(D) The plan view must be drawn to scale, showing the point of service entrance into the building. If the building sets back from the property line, the underground service feeder must be shown, including wire and raceway sizes.
(E) The arrangement of service equipment and its proximity to the point of service entrance must be shown, including the manner in which service will be extended to the service equipment. If the switchboard is free standing, the clearance around the switchboard must be shown.
(F) The location of the main switchboard and/or distribution panels in relation to the service equipment must be shown.
(G) The location of the electric service room with respect to the surrounding areas must be shown.
(H) The means of egress from the switchboard room and where it leads to must be shown. The legal exit(s) to which egress door(s) lead must also be shown.
(I) When there is more than one service location within a building, drawings must contain a notation indicating that signs are posted at the entrance door of each switchboard room showing the location of all the other switchboard rooms. The location and wording of the signs must be specified.
(J) If the existing service equipment and/or point of service entrance is to be discontinued, the drawings must so state.
(K) If existing service equipment is to remain in conjunction with new service equipment and is to be supplied by the same service entrance, the drawing must indicate the make and size of the existing service equipment, and the type and size of the fuses and/or circuit breakers in the existing equipment.
(L) The drawing must show grouping of service equipment at the point of service entrance.
(M) The drawing must show a method of cooling, with or without fresh air circulation, to prevent temperature rise in the room, when the service equipment totals 2000 KVA or larger (this may be in the form of a note on the drawing).
(N) The drawing must show the available short circuit current at the point of service entrance and at the point of change in the interrupting rating of the overcurrent protection. Where used, series ratings must be indicated.
(O) A statement confirming that all fuses and/or circuit breakers have been coordinated for selective short circuit overcurrent protection must be on the drawing.
(P) A one-line diagram must be submitted indicating the service equipment and the distribution equipment up to and including the second level overcurrent protection, showing all overcurrent devices and electrical equipment with their ampere rating, make and type, interrupting current ratings and wire sizes. Frame and trip sizes for circuit breakers must be indicated.
(Q) Drawings must indicate that transformers are properly grounded. Service and distribution equipment proposed for future installation must be marked on the drawings as "future."
(R) All voltages must be clearly shown on the drawings, which must include voltages pertaining to all of the equipment overcurrent protection up to and including the second level protection.
(S) When a generator (or other non-utility source) is part of a 1,000 KVA or greater submission and the generator itself is rated below 1,000 KVA, a one line diagram must be submitted showing how the generator is connected to the normal service. The drawings must include the grounding of the generator frame and neutral bonding if needed (four pole transfer device). If the generator is rated 1,000 KVA or larger, a room layout must be submitted along with a one line diagram.
(iv) A selective coordination report prepared by a professional engineer must be filed with the Department prior to electrical inspection. Such engineer may be different from the applicant. The report must show selective coordination was achieved, including but not limited to time-current curves (TCCs) and short circuit calculations. A summary of findings must also be included to ensure compliance with applicable codes and standards.
(v) Where installation of equipment differs from the original approved drawings, amended drawings showing the as-built condition must be filed with the Department prior to electrical inspection.
(vi) The submission of any other documentation requested by the Department.
(2) Special permission. Special permission may be granted in accordance with § 28-103.3 of the Administrative Code and § 90.4 of the Electrical Code. Request for special permission must be made electronically and comply with the following:
(i) Demonstrate practical difficulty and provide supporting documentation.
(ii) Include proposed equally safe alternative methods.
(iii) Include the appropriate filing fee as follows:
(A) For requests made under the 2011 Electrical code, a filing fee of $350.00 must be paid for each submission made where a violation was issued for failure to comply with the Electrical Code.
(B) For requests made under the 2025 Electrical Code, a filing fee must be paid as specified for a variation of the Construction Codes in 1 RCNY § 101-03.
(3) Office of Technical Certification and Research ("OTCR") review. Filings for OTCR review of electrical equipment not otherwise approved for use by the Electrical Code must comply with the following:
(i) The submission, including a cover letter, notarized application and payment, must be filed with OTCR or electronically, as the Commissioner may require.
(ii) A filing fee of $600.00 must be paid for each submission.
(iii) Payment must be made" in a form and manner as provided by the Commissioner.
(iv) The submission must contain the following:
(A) A cover letter indicating the following:
1. Type/model numbers of material/equipment being submitted for approval.
2. Items included in support of the submittal.
3. Explanatory information/comments, if applicable.
(B) A completed and notarized application for review.
(C) Two (2) brochures, or catalog data sheets, and a set of unmounted photographs or photographs.
(D) A complete test report that includes a conclusion sheet from a laboratory acceptable to the Commissioner.
(E) Equipment samples only when requested by OTCR.
Additionally, a field evaluation may be performed whenever the Electrical Code or the rules of the department require electrical equipment be listed or labeled and the electrical equipment is not so listed or labeled.
(c) Compliance with the New York City Energy Conservation Code. All electrical submissions must comply with the requirements of the Energy Conservation Code where applicable.
(d) Amendments. Any amendment made to plan reviews that were filed under the Electrical Advisory Board (EAB), including Post Approval Amendment (PAAs), must be refiled in accordance with the requirements of this rule.
(Amended and renumbered* City Record 6/11/2019, eff. 7/11/2019; amended City Record 11/21/2025, eff. 12/21/2025)