§ 91.2700 — BASIC PROVISIONS
Los Angeles Municipal Code (2026 Rev. 9, current through legislation effective June 30, 2026) · Los Angeles Municipal Code § 91.2700
Corpus is an independent public-information project, not the official City of Los Angeles website. Stable reference URL
SEC. 91.2700. BASIC PROVISIONS.
(Amended by Ord. No. 187,719, Eff. 1/23/23.) Chapter 27 of the CBC is hereby adopted by reference, except that Los Angeles Municipal Code Subsections 91.2702.2.11.1, 91.2702.2.16.1, and 91.2702.2.19.1 are added. 91.2702.2.11.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.) 91.2702.2.16.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.) 91.2702.2.19.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)