SEC. 94.2030.0. FIRE PUMPS AND DRIVERS.

(Amended by Ord. No. 188,797, Eff. 12/31/25.) Chapter 35 of the 2025 California Building Code to the extent it adopts and amends NFPA 20 is adopted by reference and Los Angeles Municipal Code Subsections 94.2030.1, 94.2030.2, and 94.2030.3 are amended or added to read as follows: 94.2030.1. Comply with the fire pump provisions in Chapters 4 and 9 of the California Building Code. 94.2030.2. NFPA 20 Sec. 4.16.11 is added to read as follows: 4.16.11. Fire Department Connections. Fire Department connections shall not be connected to the suction side of the pump. 94.2030.3. The discharge from the test header shall terminate to the fire storage tank when available and shall be readily accessible for testing and maintenance.