18-28-708.1 General.
Combustion air ducts shall: 1. Be of galvanized steel complying with Chapter 6 or of equivalent corrosion-resistant material approved for this application. Exception: Within dwelling units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one required fireblock is removed. 2. Have a minimum cross-sectional dimension of 3 inches (76 mm). 3. Terminate in an unobstructed space allowing free movement of combustion air to the appliances. 4. Have the same cross-sectional areas as the free area of the openings to which they connect. 5. Serve a single appliance enclosure. 6. Not serve both upper and lower combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combustion air. 7. Not be screened where terminating in an attic space. 8. Not slope downward toward the source of combustion air, where serving the upper required combustion air opening.