18-29-606.5.1.1.2 Compression tank.
Each compression tank shall be so connected that the air content thereof shall be no less than 25 percent of its total capacity. Each compression tank shall be provided with a sludge drain pipe which shall be connected to such tank at the lowest level of the bottom section thereof and shall discharge through an indirect connection into the drainage system with a minimum air gap of 6 inches (150 mm).