§ 18-29-607.3 — Thermal expansion control

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-607.3

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

18-29-607.3 Thermal expansion control.

Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion control device shall be connected to the water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and backflow preventers. Thermal expansion tanks shall be sized in accordance with the tank manufacturer's instructions and shall be sized such that the pressure in the water distribution system shall not exceed that required by Section 18-29-604.8. (Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 27)