§ 14E-5-518 — Assembly occupancies

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14E-5-518

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference URL

14E-5-518 Assembly occupancies.

The provisions of Article 518 of NFPA 70 are adopted by reference with the following modifications: 1. Revise subsection 518.4(A) to read: "General. The fixed wiring methods shall be metal raceways, flexible metal raceways, or Type MI cable. Exception: Fixed wiring methods shall be as provided in Article 640 for audio signal processing, amplification, and reproduction equipment, in Article 800 for communications circuits, in Article 725 for Class 2 and Class 3 remote-control and signaling circuits, and in Article 760 for fire alarm circuits." 2. Delete subsections 518.4(B) and (C).