§ 701.11

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 701.11

Corpus is an independent public-information project, not the official City of New York website. Stable reference URL

Section 701.11

Section 701.11 – Add a new Section 701.11 to read as follows: 701.11 Generator Supply Conductors without Overcurrent Protection. (A) Conductors Ampacity. See 445.13 of this code. (B) Installation of Generator Conductors. Conductors from the generator output terminal to the first overcurrent device shall be installed in accordance with 230.6. (C) Overcurrent Devices. The number of overcurrent devices supplied by the generator shall not be limited.