Section 507.5.1 amended—Where Required.
Riverside Municipal Code § 16.32.315
in effect16.32.315 - Section 507.5.1 amended—Where Required.
Section 507 is amended by amending Section 507.5.1 in its entirety to read as follows:
Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 350 feet (107 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
EXCEPTION:
1. For Group R-3 and Group U occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, the distance requirement shall be not more than 500 feet (183 m).
(Ord. 7745, § 1(Exh. A), 2025)