Fire Pump and Riser Room Size
Baltimore City Code, Building Codes, Part II, Section 902
in effectSection 902. Fire Pump and Riser Room Size
902.1 Pump and riser room size.
902.1.1 Access. {As in IBC}
902.1.2 Marking on access doors. {As in IBC}
902.1.3 Environment. {As in IBC}
902.1.4 Fire Pump Location.
Fire pump and associated equipment shall be located in a separate room that is enclosed with 2-hour fire-resistance-rated fire-separation assemblies. Installation shall comply with requirements of Article 695 of Part III (“Electrical Code”) of this Code.
(Ord. 24-341 Section 1.)