Philadelphia Code Subcode R, § R703 EXTERIOR COVERING
SECTION R703 EXTERIOR COVERING
* * *
[Pursuant to the UCC, delete Section R703.2 and replace as follows:]
R-R703.2 Water-resistive barrier. Not fewer than one layer of water-resistive barrier shall be applied over studs or sheathing of all exterior walls with flashing as indicated in Section R703.4, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer. The water- resistive barrier material shall be continuous to the top of walls and terminated at penetrations and building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section R703.1. Where the water-resistive barrier also functions as a component of a continuous air barrier, the water-resistive barrier shall be installed as an air barrier in accordance with Section N1102.4.1.1. Water-resistive barrier materials shall comply with one of the following:
1. No. 15 felt complying with ASTM D226, Type 1.
2. ASTM E2568, Type 1 or 2.
3. Foam plastic insulating sheathing water-resistive barrier systems complying with Section R703.1.1 and installed in accordance with the manufacturer’s installation instructions.
4. ASTM E331 in accordance with Section R703.1.1.
5. Other approved materials in accordance with the manufacturer’s installation instructions.
No.15 asphalt felt and water-resistive barriers complying with ASTM E2556 shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm), and where joints occur, shall be lapped not less than 6 inches (152 mm).
Exception: A water-resistive barrier shall not be required in unconditioned detached tool sheds, playhouses, and other similar accessory structures provided all of the following requirements are met:
1. Exterior wall covering is limited to siding that is attached directly to the studs.
2. Exterior walls are uninsulated.
3. Interior side of exterior walls has no wall covering or wall finishes.
* * *
[Pursuant to the UCC, delete Section R703.3.1 and replace as follows:]
R-R703.3.1 Exterior soffit installation. Exterior soffits shall comply with Section R704.
* * *
[Pursuant to the UCC, delete Section R703.4.1 and replace as follows:]
R-R703.4.1 Flashing installation at exterior window and door openings. Flashing at exterior window and door openings shall extend to the surface of the exterior wall finish or to a water-resistive barrier complying with Section R-R703.2 for subsequent drainage. Air sealing shall be installed around all window and door openings on the interior side of the rough opening gap. Mechanically attached flexible flashings shall comply with AAMA 712. Flashing at exterior window and door openings shall be installed in accordance with one or more of the following:
1. The fenestration manufacturer’s installation and flashing instructions, or for applications not addressed in the fenestration manufacturer’s instructions, in accordance with the flashing or water-resistive barrier manufacturer’s instructions. Where flashing instructions or details are not provided, pan flashing shall be installed at the sill of exterior window and door openings. Pan flashing shall be sealed or sloped in such a manner as to direct water to the surface of the exterior wall finish or to the water resistive barrier for subsequent drainage. Openings using pan flashing shall incorporate flashing or protection at the head and sides.
2. In accordance with the flashing design or method of a registered design professional.
3. In accordance with other approved methods.
* * *
[Pursuant to the UCC, delete Section R703.7 and replace as follows:]
R-R703.7 Exterior plaster (stucco). Installation of exterior plaster shall be in compliance with ASTM C926-2018B, ASTM C1063-2018B and the provisions of this code.
* * *